CHAPTER 7
PUBLIC WORKS RULES AND REGULATIONS
Sec. 7-1 Title.
Sec. 7-2 Scope of Code.
Sec. 7-3 Definitions.
Sec. 7-4 Safety Provisions, Construction.
Sec. 7-5 Safety Provisions, Fire Protection.
Sec. 7-6 Health and Sanitation.
Sec. 7-7 State Building Code.
Sec. 7-8 Alternate Materials.
Sec. 7-9 Administration.
Sec. 7-10 Permits and Fees.
Sec. 7-11 Inspection.
Sec. 7-12 Penalties.
Sec. 7-13 National Electrical Code.
Sec. 7-14 Plumbing Code.
CHAPTER 7 - PUBLIC WORKS RULES
AND REGULATIONS
Sec. 7-1 Title
This article shall be cited as the Building Code of the Town of Kentland
and is declared to secure the beneficial interest and purposes intended,
and applies to the incorporated area of the Town of Kentland, Newton County,
Indiana.
Sec. 7-2 Scope of Code
(a) This Article provides for all matters concerning the construction,
remodeling, alterations, repairing, wrecking, moving, or removal of buildings
and structures erected or to be erected in the Town; the safety of workers
and others during these operations, and the safe use of such buildings
or structures.
(b) The Building Inspector shall have the power to
construe and enforce all of the provisions of the Building Code, as it
may be amended from time to time.2
Sec. 7-3 Definitions
The following terms shall be defined as follows:
(a) Approved: Approval by the building inspector under the provision
of this Article or by other authority designated by law to give approval
of the matter in question.
(b) Area: The maximum horizontal area of the building at finished
grade exclusive of unroofed porches, terraces, steps and area-ways.
(c) Basement: That portion of a building, between floor and ceiling,
which is less than 50 percent underground. when 50 percent or more of
the space in a basement is used for a habitable room it shall be counted
as a story.
(d) Building Inspector: The person charged with administration
and enforcement of this Article.
(e) Ceiling Height: The vertical distance between the floor and
ceiling. Where a finished ceiling is not provided the underside of joists
shall determine the upper point of measurement.
(f) Cellar: That portion of a building, between floor and ceiling,
which is more than 50 percent underground.
(g) Concrete:
(1) Plain-- Concrete cast in place without metal reinforcement or reinforced
only for shrinkage or temperature changes.
(2) Reinforced--Concrete in which steel rods or mesh are embedded to
increase strength.
(h) Dwelling: A building designed or occupied as the living quarters
for not more than two families or households and usually equipped with
cooking, bathing, heating, and toilet facilities.
(i) Erected: Includes any construction, reconstruction, enlargement,
movement or physical operation on either the dwelling or on the land required
for the dwelling. Excavation, fill, drainage and the like shall be considered
a part of erection.
(j) Floor Area of a Room: The number of square feet of floor space
within the walls of a room.
(k) Grade, Finished: The line formed at the junction of a building
and the area immediately surrounding the building.
(1) Habitable Room: A room occupied by or designed for occupancy
by one or more persons for living, sleeping, eating or cooking including
kitchens serving a dwelling unit but not including bathrooms, water-closet
compartments, laundries, serving and storage pantries, corridors, cellars,
attics, recreation rooms, and spaces that are not used frequently or during
extended periods.
(m) Incombustible: Material that will not of and by itself ignite
when its temperature and that of the surrounding air is 1,200° Farahenheit
(649° Centigrade).
(n) Lintel: A horizontal structural member supporting masonry
above any opening in a wall or partition.
(o) Load Dead: The weight of walls, floors, roofs, partitions
and other permanent portions of the structure.
(p) Lot: A portion or parcel or land considered as a unit devoted
to a certain use or occupied by a building or a group of buildings united
by a common interest or use, and the customary accessories and open spaces
belonging to same.
(q) Lot Line: A line dividing one lot from another or from a street
or other public place. In case any part of a lot lies adjacent to a public
right-of-way or easement, the lot line of that part shall be right-of-way
line or easement boundary crossing such part.
(r) Masonry: Stone, brick, structural clay tiles, concrete masonry
units, gypsum tile or block, structural glass block or other similar building
units or materials or a combination of same bonded together with mortar.
Masonry also includes plain concrete.
(s) Partition,bearing: A partition which supports any vertical
load in additional to its own weight.
(t) Partition,non-bearing: A partition which supports no load
other than its own weight.
(u) Pier: An isolated column of masonry. A bearing wall not bonded
at the sides into associated masonry and whose length does not exceed
four times its thickness.
(v) Walls, veneered: A wall having a facing which is not attached
and bonded to the backing so as to form an integral part of the wall for
purposes of load bearing and stability.
(w) Yard: A space open to the sky and unoccupied or unobstructed
except by encroachment or structures specifically permitted by this Code
on the same lot with a dwelling. All yard measurements shall be the minimum
distances between the front, rear, or side year line, as the case may
be, and the nearest point of the dwelling including enclosed or covered
porches. Every part of every yard shall he accessible from every other
part of the same yard.
1. Yard, front--A yard across the full width of the lot extending from
the front line of the dwelling to the front line of the lot.
2. Yard, side--A yard extending from the front yard or front lot line
to the rear yard or real lot line, and from the side line of the dwelling
to the side lot line nearest that side of the dwelling, or of any accessory
building attached thereto.
3. Yard, rear-- A yard across the full width of the lot extending from
the real line of the dwelling to the real line of the lot.
(Ord. No. 221, §1, 12-3-51)
Sec. 7-4 Safety Provisions,
Construction
(a) Quality of Materials and Workmanship
All building materials and workmanship shall be of good quality conforming
to generally accepted standards. Except as may be otherwise provided
in this Article, the standards of the National Bureau of Standards are
hereby declared to be acceptable good practice.
(b) Masonry Mixes
1. Mortar
a. Proportions: Mortars of the following proportions measured by
volume with the sand in a damp loose condition, shall be acceptable
for the specific use mentioned in this section:
Type A. One part of portland cement to not more than 3 parts of
sand with an addition of hydrated lime or lime putty of not more
than 25 percent of the cement.
Type B--One part of portland cement, one part of hydrated lime
or lime putty, and not more than 6 parts of sand. One part of prepared
masonry cement conforming to Type II of Federal Specification SS-C-181B
to not more than 3 parts of sand.
b. Use: Type A mortar shall he used for all below-grade masonry construction.
Type A or B mortar shall be used for all above-grade construction.
2. Concrete
a. Workable concrete. Water used in mixing concrete shall be clean
and free from deleterious amounts of acids, alkalies or organic materials.
The maximum size of concrete aggregates shall be not larger than 1/5th
of the narrowest dimension between forms of the member for which the
concrete is to be used, nor larger than 2 1/2 inches. Workable concrete
shall be produced in accordance with the following tables for the
particular use specified:
| |
Maximum gallons
of Water per Sack of Cement with Sand of Moisture Content Indicated |
Maximum Cubic Feet of
Total Aggregate per Sack of Cement |
| Type of Concrete and Use |
|
|
|
|
| |
|
|
|
|
| |
Dry |
Average |
Wet |
|
| Type A-All concrete exposed to the weather
or to water pressure, or reinforced |
6 |
5 1/2 |
4 3/4 |
6 |
| Type B-All other concrete, except Type
C |
7 |
6 |
5 1/4 |
6 1/2 |
| Type C-Footings |
7 1/2 |
6 1/2 |
5 1/2 |
7 1/2 |
*Proportion of sand (passing 1/2 inch screen) to coarse aggregate (retained
on 1/2 inch screen) shall be not less than 35 percent nor more than 50
percent by volume.
b. Protection. When the temperature of the surrounding air is less
than 40° Fahrenheit, the materials shall be heated and the concrete
protected for as much time as is necessary to insure proper curing.
All concrete shall be kept wet for at least five (5) days. All masonry
shall be protected against freezing for a least 48 hours after placing.
Unless adequate precautions against freezing are taken, no masonry shall
be laid when the temperature is below 32° Fahrenheit on a rising
temperature or below 40° on a falling temperature at the point
where the work is in progress. In hot, dry weather, precautions shall
he taken to prevent too rapid drying by sprinkling or shielding with
damp earth, burlap or similar protective covering. No fresh masonry
construction shall be made upon frozen concrete.
c. Other requirements. For design principles and practices not specifically
mentioned in this section, the standards set forth in the "Building
Regulations for Reinforced Concrete" of the American Concrete Institute
ACI-318, shall be acceptable.
(c) Footings and Foundations
1. General: All dwellings shall be placed on a masonry foundation.
All footings and piers shall be carried below local frost level, shall
bear on undisturbed soil, and shall be designed to properly and safely
distribute the superimposed load. Where soil conditions are unstable,
the building inspector may require additional provisions to insure stability.
Drain tile shall be used around basement foundations where conditions
require it.
2. Size of footings and piers: Footings for all load bearing walls
shall be of concrete at least 16 inches wide and 8 inches deep. Footings
of piers shall have a minimum area of 4 square feet and 12 inches deep.
3. Chimney footings: Chimney footings shall have a minimum projection
of 6 inches beyond outside dimensions of chimney foundation and a minimum
depth of 12 inches.
4. Foundation walls: Foundation walls of all dwellings shall center
on footings and shall be of the following thickness: If built of rubble
stone, the thickness shall be not less than 18 inches. If built of brick,
concrete, hollow blocks or solid blocks, the thickness shall be not
less than twelve (12) inches; provided that when such walls of dwellings
do not extend more than five (5) feet below the adjacent ground level,
the minimum thickness of masonry or concrete walls shall be eight (8)
inches. Foundation walls shall never be thinner than the wall being
supported.
5. Openings for inspection and repair: An opening of not less than
18 inches high and 2 feet wide shall be installed to provide access
for inspection and repairs of each unexcavated space under wood or metal
floor construction, or under concrete slabs where piping, duct work,
etc., requiring periodic inspection or repair are located.
6. Wall vents: Wall vents proportioned on a basis of 64 square inches
for each 25 lineal feet of exterior wall shall be installed for ventilating
all dead air spaces under wood or metal floor construction and each
such space shall have vents in at least two walls, except that only
1 vent into a basement or cellar will be acceptable. Non-corrodible
screening or not over 1/2 inch spacing shall be installed in
each outside vent opening.
7. Concrete slabs on ground: Dwellings constructed on concrete slabs
will be acceptable when the construction of the slab meets the approval
of the building inspector.
(d) Minimum Design Loads.
1. All floors for one-and two-family dwellings shall be designed for
the dead load plus a live load of not less than 40 pounds square foot
of floor area. All roofs shall be designed for the dead load plus a
live load of not less than 30 pounds square foot of horizontal projection.
(e) Wood Construction
In General:
1. Size of lumber members: Minimum size of lumber members
required by. this Code refer to nominal sizes. American Lumber Standards
for dressed sizes shall be accepted as the minimum net sizes conforming
to nominal sizes. Computations to determine the required sizes of
members shall be based on the net dimensions (actual size) and not
the nominal sizes.
2. Splicing: Splicing of wood joists between bearing points
will not be permitted.
3. Girders:. Girders may be structural steel, solid wood,
built-up wood or reinforced concrete. All built-up wood girders shall
have joints broken at no less than 4 foot intervals.
4. Headers and Trimmers: Headers and trimmers shall be doubled
except that headers 4 feet or less in length may be of single thickness,
provided the headers are supported in metal joist hangers, or on columns
or posts, or on not less than 2 inch by 3 inch ledger boards and header
is secured by spikes driven through one thickness of the trimmer into
the ends of the headers. Headers receiving more than 4 tail beams
shall have ends supported in metal joist hangers.
5. Lapped Joists: Ends of lapped joists shall rest on girders
or on bearing partitions and shall be securely nailed to plate and
to each other.
6. Bridging Floors: Including attic floor, and flat roof joists
shall be cross-bridged at intervals not to exceed 8 feet and double
nailed at each end.
7. Defects: Where the structural strength of framing members
is definitely impaired by inherent defects or by cutting or drilling,
such members shall be reinforced or replaced as required by the building
inspector.
8. Access: An opening not less than 24 inches by 30 inches
for access into each attic space shall be provided.
9. Ventilation: All attics and spaces between flat roofs and
ceilings shall be ventilated by screened louvers or other means approved
by the building inspector.
10. Collar Beams: When ceiling joists does not serve as ties
for the rafters, collar beams of 1 by 6's or 2 by 4's shall be installed
on at least each 3rd pair of roof rafters and shall he securely nailed
to the rafters. Maximum spacing of collar beams, 5 feet on center.
11. Valley Rafters: The depth of ridge boards and valley rafters
shall not be less than the ends of the abutting rafters. Valley rafters
shall be not less than 2 inches thick for spans over 12 feet shall
not be less than 4 inches thick. All rafters shall be securely spiked
to the supporting members.
12. Double Rafters: All openings in roof construction for
dormer windows which are not supported on partitions shall be framed
with double rafters and headers.
For Exterior Walls:
1. Framing: All external wall covering materials shall be
moisture-resistant, of sufficient stiffness and properly anchored
to remain in place during high winds and be reasonable permanent,
provided however, that no type of material shall be used other than
those types approved by the Building Inspector. A list of such approved
materials may be obtained from the Building Inspector. All exterior
wood or metal stud walls shall provide strength and rigidity equivalent
to the following:
2 inch by 4 inch wood studs spaced not more than 16 inches on
center for walls supporting floor loads.
2 inch by 4 inch wood studs spaced not more than 24 inches on
center for walls that do not support floor loads.
All studs shall be securely fastened to plates top and bottom, and
diagonally braced at outside corners of walls. Walls shall have corner
posts either built-up or solid of not less than three 2 by 4's. Top
plates shall be not less than doubled 2 by four's which shall lap
at all intersecting partitions. All such laps shall be securely spiked.
All window and door openings shall have studs doubled on jambs. The
inner stud shall be cut to receive the header over the opening and
shall extend in one piece from header to bearing. Headers over all
openings shall be doubled and shall be set on edge. In lieu of headers,
trussed construction may be used. Spans for headers shall not exceed
the following of the size given:
| Spans up to 4 feet. |
two 2 by 4's |
| Spans 4 feet to 5 1/2 feet |
two 2 by 6's |
| Spans 5 1/2 feet to 7 |
two 2 by 8's |
| Spans over 7 feet |
two 2 by 10's |
2. Anchorage: The sills of frame walls supported directly
on masonry shall be not less than 2 inches thick and not less in width
than that of the width of the studs. Such sills shall be bolted to
the masonry at corners and between corners with 1/2 inch bolts not
less than 7 inches in length and spaced not more than 6 feet apart.
3. Sheating may be of wood structural insulation board, gypsum
board, plywood, or other materials approved by the building inspector.
For Interior Partitions:
1. Bearing Partitions: Studs of all bearing partitions and
studs of all non-bearing partitions exceeding 6 feet of unsupported
length which contain openings shall be made up of 2 by 4's spaced
not more than 16 inches on center and set the 2 inch way.
2. Openings: All openings in interior bearing partitions shall
have jambs and heads double-framed same as required for exterior openings.
3. Top Plate: The top plates of all bearing partitions shall
be doubled. All partition plates shall lap at all intersecting partitions
and at outside walls, and shall be securely spiked.
4. Sole Plate.: When partitions frame on top of the joists
or subfloor, the studs shall bear on a sole plate at least 2 inches
thick.
(f) Masonry Construction
For Walls:
1. Solid Brick Walls: Solid brick bearing walls shall be not
less than 8 inches thick. There shall be a header course in all brick
walls at least every seventh course on both sides of the wall or there
shall he at least one full-length header in every 1 1/2 square feet
of wall surface.
2. Hollow Masonry Unit Walls: The minimum thickness bearing
walls of structural clay tile or concrete masonry units shall be not
less than 8 inches. Hollow masonry units shall have full mortar coverage
on vertical and horizontal edges of the face shells. Where 2 or more
hollow units are used to make up the thickness of a wall, the inner
and outer course shall be bounded at vertical intervals not exceeding
34 inches by lapping at least 4 inches or by lapping with units at
least 50 percent greater in width than the units below.
3. Brick Veneered Walls: Thickness of brick veneer shall be
not less than 3 3/4 inches properly anchored with rust-resisting
wall ties and with at least one tie every three (3) square feet. The
veneer shall rest on the foundation. Two inch brick veneer may be
used for one-story dwellings upon approval by the building inspector.
For Lintels and Arches:
1. The masonry above openings shall be supported by arches of masonry
or lintels of steel or reinforced concrete, which shall bear on the
wall at each end for not less than 4 inches and shall be supported
as required for concentrated loads.
For On Masonry Construction:
1. All structural members producing concentrated loads shall have
bearings at least 3 inches in length upon solid masonry not less than
4 inches thick. Metal bearing plates of adequate design and dimensions
but not less than 1/4 inch thick may be used.
For Support on Wood:
1. No masonry construction shall be supported on wood construction.
No timber except nailing blocks not exceeding an ordinary brick in
size, shall be built in as a part of masonry walls.
(Ord. No. 221, §2, 12-3-51)
Sec. 7-5 Safety Provisions, Fire Protection
(a) Firestopping
In General:
1. Firestopping shall be supplied at the locations specified in this
section and shall be so arranged as to cut off all concealed draft
openings and form an effectual fire barrier between stories and between
the upper story and the roof space.
For Exterior Walls:
1. Wood Construction: Exterior walls of wood construction shall be
properly firestopped at each floor level and at the level where the
roof rafters connect with the wall plate.
2. Furred Space: For all masonry walls that are furred or studded
off, the space created by the furring or studding shall be properly
firestopped once in each story. Space around chimneys shall be firestopped
with incombustible material.
For Partitions:
1. Where stud partitions rest directly over each other and the studs
run down between the floor beams and rest on the top plate of the
partition below, the spaces between the studding shall be properly
firestopped.
For Stairs:
1. The space between stair carriages shall he firestopped by a header
beam at top and bottom. Where a stair run is not all in one room or
where a closet is located beneath the stairs, the stair carriage shall
have an intermediate firestop so located as to cut off communication
between portions of the stairs in different rooms of between the closet
and the room in which it is placed. Such stops shall be made of plank
or other suitable material.
For Pipes and Ducts:
1. Where any pipe or duct passes through a floor, the space between
the pipe or duct and the floor construction shall be firestopped.
Where the installation of pipes, ducts, or conduits in walls, floors
or partitions requires the removal of any firestopping, the spaces
around the pipes, ducts or conduits at such points where such firestopping
was removed, shall be tightly filled with asbestos, mineral wool or
other incombustible material.
Inspection:
1. No firestopping shall be concealed from view until opportunity
has been given the building inspector to inspect the same.
(b) Chimneys, Flues, and Smoke Pipes.
In General:
1. Chimneys shall be constructed in accordance with good practice
provided that the specific requirements of this Article shall be observed.
Chimney Regulations:
1. Materials: Chimneys shall be constructed of brick, stone
or of reinforced concrete. When constructed of laid-up masonry units,
such units shall be not less than 3 1/2 inches wide laid with full
head and bed joints of Type A or Type B mortar. No chimney shall be
constructed of hollow masonry units unless such units shall first
have been proven to the satisfaction of the building inspector to
be the equal of or superior to solid masonry units. Flue linings shall
be required under conditions indicated in another part of this section.
Variations from specific requirements noted herein shall he subject
to the approval and labeling requirements of the building inspector.
2. Foundations: Masonry or reinforced concrete chimneys shall
not rest upon or be carried by wood floors, beams or brackets, nor
be hung or supported by metal stirrups from wood construction but
shall be built upon concrete or masonry foundations or reinforced
concrete slabs properly proportioned to carry the load without danger
of settlement or cracking. The footing shall rest on solid. earth
and shall be carried below the frost level.
3. Bonding: Masonry or reinforced concrete walls of buildings
may form parts of chimneys when the chimney walls are securely bonded
into the walls of the building and when the flue is lined with flue
lining the same as an independent chimney.
4. Corbeling of Chimneys: Corbeled chimneys shall not be supported
by hollow walls, cavity walls or walls of hollow units. Solid walls
supporting corbeled chimneys shall not be less than 12 inches thick
and corbeling shall not project more than 1 inch per course and not
more than 6 inches in any case. The total offset, overhead or corbel
of an independent chimney shall not exceed 3/8 of the width of the
chimney in the direction of the offset.
5. Height: Chimneys shall be built at least 3 feet above flat
roofs provided that the tops of chimneys shall not be below the tops
of adjacent parapet walls. In the case of sloping roofs, chimneys
shall be not less than 2 feet above the ridge of the roof that the
chimney penetrates and not less than 2 feet above the highest ridge
within 10 feet of the chimney. Unless as provided with a stone, terra-cotta,
concrete, cast iron or other approved cap or top, the chimney lining
shall project not less than 2 inches. No chimney top shall decrease
the required flue area.
6. Concrete Chimneys: Concrete for chimneys cast in place
shall flow readily, be well-rodded and shall be reinforced both vertically
and horizontally.
7. Flashing: Connections between chimneys and roofs shall
be made with cap and base flashing of sheet metal or other approved
material, arranged to allow for any lateral or vertical movement between
the chimney and roof.
8. Changes of Interior Dimensions: No change in the interior
dimensions of chimneys. shall be made within a distance of 6 inches
above or below the rafters or roof joists.
Flue Regulations:
1. General: Except as otherwise provided in this Article,
every heating apparatus or heat producing unit referred to in this
Article shall be connected with a flue conforming to the provisions
of this section.
2. Flue Linings: Chimneys built of brick, stone or other masonry
units with walls less than 8 inches thick shall be lined throughout
with fireclay or other refractory clay lining not less than 5/8 inches
thick, provided that metal or other approved flue liners may be inserted
in the flue to reduce it to a desired size.
3. Separation: When two or more flues are contained in the
same chimney, withes or brick or mortar not less than 3 3/4 inches
thick shall be provided at intervals not exceeding 30 inches horizontally,
but not more than 2 flue sections shall be placed side by side without
such separation. There the flue linings are not separated by withes,
the joints shall be staggered and the vertical distance between the
joints in adjoining flue linings shall be not less than 7 inches.
4. Construction: The masonry shall be built around each section
of lining as it is placed and all spaces between masonry and linings
shall be filled with mortar. Linings shall start at least 8 inches
below the center line of smoke pipe intakes or in the case of fireplaces
from the apex of the smoke chamber and shall be continuous the entire
height of the flue.
5. Cleaning: Flues shall be cleaned out thoroughly at the
time of construction and shall be left smooth on the inside.
Smoke Pipe Regulations:
1. Connect with flue
a. Connection Required. Every smoke pipe shall come with
a flue by means of a tight joint.
b. Number Limited. Not more than one smoke pipe shall be
connected to a flue at the same level. A vent from a gas burning
appliance may connect into the same flue as a smoke pipe providing
the connection is above a smoke pipe.
c. Thimbles. Smoke pipes shall enter chimneys through a
fire-clay or metal thimble or flue ring of masonry. Neither the
intake pipe nor the thimble shall project into the flue.
2. Passage through combustible construction
a. Ceilings, Roofs and Floors. No smoke pipe shall pass
through a ceiling, walls, floor or roof construction of combustible
materials Vents for gas burning appliances shall not be construed
to be smoke pipes.
b. Partitions. Smoke pipes shall not pass through combustible
partitions unless protected by double metal ventilated thimbles
8 inches larger in diameter than the pipe or 4 inches larger in
diameter than the pipe with the space between the pipe and thimble
solidly filled with approved incombustible insulating material,
or unless protected by a concentric sleeve of diameter 2 inches
larger than the pipe with the space between filled solidly with
incombustible insulating material and the outside surface of the
sleeve distant at least 2 inches from combustible material.
c. Clearance From Combustible Construction. The clear distance
in all direction between a smoke pipe and combustible construction,
including plaster on a combustible base, shall be not less than
12 inches provided that this clearance may be reduced 1/2 when such
construction is protected by a cement-asbestos board or by rock
lath and plaster 3/4 inches thick, or asbestos millboard not less
than 14 inch thick or equivalent approved covering extending the
full length of the smoke pipe and not less than 6 inches beyond
it on all sides or where plaster is on metal or wire lath.
3. Heating appliances.
a. General: Heating appliances shall be installed in accordance
with good practice provided that the specific requirements of this
Article shall be observed.
1. Combustion: Adequate facilities shall be provided in
all cases for the entrance of air to support combustion in rooms
or other spaces enclosing heat producing appliances and the area
of such facilities shall not be less than the combined outlet area
of the appliances so located.
2. Clearances for Heating Furnaces: No hot air, hot
water, steam heating or other type of furnace described herein shall
be located nearer than 24 inches in any direction to woodwork or
other combustible base, unless such furnace shall be enclosed in
a jacket providing an air space or which is insulated in an approved
manner and the combustible material is protected with 3/8 gypsum
board under 1/8 inch asbestos board, or with 3/4 inch portland cement
plaster on metal lath, or equivalent protection, in which case this
clearance may be reduced to not less than 6 inches.
3. Ducts: Warm air ducts, fittings and connections in warm
air heating plants shall be made of bright tin or of galvanized
iron or of such other incombustible material as may be approved
by the building inspector.
4. Fireplaces:
(a) Use of firebrick: The backs and sides of fireplaces shall be
of solid masonry not less than eight (8) inches in thickness. A lining
of firebrick at least 2 inches thick or other approved material shall
be provided unless the total thickness is twelve (12) inches.
(b) Incombustible hearths: Fireplaces shall have hearths of brick,
stone, tile or other approved incombustible material support by a
fireproof slab or on brick trimmer arches. Such hearths shall extend
at least 16 inches outside the chimney opening at the breast and not
less than 8 inches on either side of the fireplace opening along the
chimney breast. The combined thickness of hearth and supporting construction
shall not be less than 6 inches at any point, provided that where
designed and used for approved. gas appliances only, the construction
shall be such as shall fully meet good standard practice.
(c) Fire Prevention:
1. Clearance from combustible construction. No combustible construction
shall be placed within 4 inches of the enclosing walls of a fireplace.
Combustible or unprotected beams supporting trimmer arches at fireplaces
shall be not less than 20 inches from the chimney face. No combustible
mantel or other woodwork shall be placed within 8 inches of either
side nor within 8 inches of the top of a fireplace opening. All
spaces back of combustible mantels shall be filled with in-combustible
materials.
5. Water Heaters
(a) Water heaters shall be connected to smoke flues or outlet pipes
as herein before provided for gas appliances, provided that such connection
may be waived by the building inspector if the water heater is of
a type which cannot produce an explosive mixture or asphyxiating condition
in the room or space where it is located.
6. Electrical Wiring and Outlets.
(a) The installation of all electrical work including equipment shall
in every case be done in a safe and workmanlike manner. The regulations
of the National Electrical Code, shall be considered as good standard
practice by the building inspector. Installations shall comply with
the requirements of the electric utility company serving the area.
Such code and regulations as it applies to any dwelling shall be the
latest edition of that code effective at the time of beginning of
construction of such dwelling.
(Ord. No. 221, §3, 12-3-51)
Sec. 7-6 Health and Sanitation
(a) Open Areas: For the provision of sufficient light, air,
and ventilation, no structure shall be erected or remodeled unless provisions
for front; side and rear yards adjoining such structure are in compliance
with the requirements of the current legal Zoning Ordinance of the Town
of Kentland, Indiana, found in Chapter 10
of this Code.
(b) Water Supply: All water supply shall
be from public or quasi-public mains, when available, or from such wells
or the private sources of such type and in such location as to meet
the requirements of the County Health Officer and the standards of the
Indiana State Board of Health.
(c) Sewage Disposal: All sewage shall be
disposed of in existing sanitary sewer systems, when available, or through
the use of septic tanks, cesspools or privies which are so designed
and located as to meet the requirements of the County Health Officer
and the standards of the Indiana State Board of Health.
(Ord. No. 221, §4 12-3-51)
Sec. 7-7 State Building Code
This Article recognizes the responsibility of the Town of Kentland, Indiana,
to enforce the State Building Code as it may be amended from time to time
as it applies to all structures except residences, farm buildings and
temporary buildings. As directed by State Statute, he building inspector
charged with the enforcement of this Article shall be bound by the provisions
of applicable State Codes and Statutes.
(Ord. No. 221, §5, 12-3-51)
Sec. 7-8 Alternate Materials
The use of alternate types of materials from those specified in this
Article shall be permissible, at the discretion of the Building Inspector,
upon a showing by manufactures standards that such alternate materials
are equal to or better than those specified by this Article.
(Ord. No. 221, §6, 12-3-5)
Sec. 7-9 Administration
(a) For the purpose of enforcing the provisions of this Article the
Town Board of Trustees of the Town of Kentland shall appoint a Building
Inspector, who shall serve under the direction of the Kentland Planning
Commission.
(b) The Commission shall, by resolution, establish the duties of such
Building Inspector, supervise his activities, and together with the
Board of Trustees of the Town of Kentland, fix his compensation.
(Ord. No. 221, §7, 12-3-51)
(a) Prior to the construction, reconstruction or
remodeling of any structure within the incorporated area of Kentland,
Indiana, when the cost of such improvement exceeds five hundred ($500.00)
dollars, an application for a building permit shall be made with the
Building Commissioner on such forms as may be prescribed by the Kentland
Plan Commission.
(b) Such application shall include sufficient plans
and specifications to enable the Building Commissioner to determine
compliance with this Article.
(c) Fees for the issuance of such permits shall
be payable to the Town Clerk-Treasurer of Kentland, Indiana, and shall
be as follows:
New Construction $2.00 minimum; then 30 cents per 1000 cubic ft.
Remodeling $2.00 minimum; then 10 cents per $100 estimated cost.
(Ord. No. 221, §8, 12-3-51)
It shall be the duty of the Building Inspector to furnish sufficient
inspections on all structures to insure compliance with the provisions
of this Article, but not less than two (2) on new construction.
(Ord. No. 221, §9, 12-3-51)
Sec. 7-12 Penalties
Any resident freeholder of the Town of Kentland, Indiana, or the Planning
Commission of the Town of Kentland, Indiana, or the Board of Trustees
of the Town of Kentland, Indiana may institute a suit for injunction or
for mandatory injunction to enforce the provisions of this Article and
the proceedings for bringing any injunction action of any kind shall be
in accordance with the statutes of the State of Indiana relating to the
bringing of actions for injunctions.
(Ord. No. 221, §10, 12-3-51)
Sec. 7-13 National Electrical Code
(a) The National Electrical Code, adopted by the National Fire Protection
Association, and all amendments and supplements thereto is adopted and
by reference and made a part of this chapter.
(b) Two (2) copies of the National Electrical Code shall be kept on
file in either the office of the Clerk-Treasurer or Inspector for public
inspection.
(a) The Plumbing Rules and Regulations, Volume III, 1976 Edition, as
amended, promulgated by the Administrative Building Council of Indiana,
is adopted by reference and made a part of this chapter.
(b) Two (2) copies of the Plumbing Rules and Regulations shall be kept
on file in either the office of the Clerk Treasurer or Inspector for
public inspection.

1 I.C. 36-7-9-1 through 36-7-9-28
addresses the enforcement of building standards.
2 I.C. 36-9-20-9 addresses building
codes and restrictions on the use of property. |